This state of the art emergency communication system is modular and is designed for a variety of voice alarm guidance applications. The system quickly integrates via a single primary connection to a sounder circuit output from the host fire alarm control panel. The panel comes with a variety of pre-set configurations providing complete notification capability right out of the box.
The ZT-DVS-RM/B is a remote microphone for use with the ZT-MNS-100BAS voice evacuation panel. Only one remote microphone can be used with each audio panel. (note the ZT-MNS-100BAS panel includes a microphone).
The ZT-DVS-RM/B microphone can be located up to 100ft from the main panel and to provide paging and live ‘override’ of the pre-recorded message and alert
tones.
The microphone and interconnecting wires are supervised. A fault will cause the control boards system LED, and remote Mic Fault LED to light. The surface mounting steel enclosure provides a key locking hinged cover. The device can be placed in an entry way for access by authorised personnel only.
Technical Specification
Input Volt / Amp: 24 VDC / 0.06A
Output Compatible with ZT-MNS-100BAS
Wiring
Up to 30 metres (100 feet)
18-22 AWG, 4-conductor cable
Shielding is recommended if cable is run in same conduit with SLC
Enclosure 210mm H x 184mm W x 89mm D
Colour Red