FP 2 Zone Conventional Fire Alarm Panel
FP 2 Zone Conventional Fire Alarm Panel is backordered and will ship as soon as it is back in stock.
Couldn't load pickup availability
                    
                      Description
                      
                      
    
                    
                  
                  Description
- Installer-friendly design.
 - Robust metal enclosure c/w lift off lid & heavy-duty base connections.
 - Two conventional Zone circuits.
 - Two conventional Sounder circuits.
 - Separate indicators for open & short circuit fault, sounder fault and battery/power supply fault.
 - Non-latching class change sounder output, latching fire & non-latching fault outputs (via optional expansion loom).
 - Short circuit=fire facility (pre-1980 BS, no resistors in call points, selectable on a zone by zone basis).
 - Ancillary connections for repeaters and other system add-ons including fault relay modules, fire relay modules, sounder delay relay modules, sounder extender kits, etc).
 - Multi-lingual variants (subject to quantities).
 - Space for 2 x 12V 2.3Ah VRLA batteries.
 - Compatible with virtually all known conventional fire detectors including C-TEC’s ActiV range.
 - Designed to comply with BS 5839-4 (this panel in not compliant with EN54-2/4 and should NOT be used in new UK or European installations).
 
Technical Specifications
| Compatibility | 
 Designed to comply with the requirements of BS5839-4 (for head-out monitoring use 1 x BF378M module per zone).  | 
|---|---|
| Mains supply | 
 230V 50/60Hz.  | 
| Internal power supply | 
 27V nominal.  | 
| Total output current limited to | 
 800mA @ 230V.  | 
| Quiescent current | 
 40mA (with no mains supply, fault beeper muted, no aux. output connections, EOL devices and resistors only fitted to detector and sounder loops).  | 
| Max battery size and type | 
 2 x 12V 2.3Ah VRLA connected in series.  | 
| No. of detector zone circuits | 
 2 (Max. length per circuit is 500m). Additional Zones cannot be added to this panel. For head out monitoring 1 x BF378M is required per Zone.  | 
| Call point resistor value | 
 470 to 680Ω.  | 
| Max. devices per detector zone | 
 20 detectors (max. detector current 2mA). No limit for manual call points.  | 
| No. of conventional sounder circuits | 
 2 (Max. length per circuit is 500m).  | 
| EOL resistor value | 
 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).  | 
| Max. sounder output current | 
 800mA (to all outputs). Outputs are fused at 1A.  | 
| Auxiliary relays | 
 1 x onboard relay (1A, 30 VDC, follows sounders). Additional relays available via optional expansion looms (FF374FR, FF374FDR & FF374DT).  | 
| Open collector outputs | 
 Available via optional expansion loom FF374X.  | 
| Auxiliary inputs | 
 Available via optional expansion loom FF374X..  | 
| Indicators | 
 Mains on; Zone Fire; Zone Fault; Sounder Fault; Battery/Power Supply Fault; O/C fault; S/C fault; Zone isolated; Engineer Test selected.  | 
| Controls | 
 Reset; Resound; Test Zone Lamps; Evacuate; Silence Alarm Sounders; Silence Fault Sounders; Revert to S/C equals Fire; OMT, Zone Isolate. Keyswitch.  | 
| Product dimensions (mm) | 
 322 W x 267 H x D 92mm.  | 
| Construction & finish | 
 Metal lid and base.  | 
| IP Rating | 
 IP30.  | 
| Weight | 
 4.3kg.  | 
| Operating conditions/temperature | 
 -5ºC to +40ºC. Max relative humidity: 95%.  | 
| Notes | 
 Repeater info: Up to 3 repeaters per main. 5 cores plus 1 per zone. Max. cable length 200m.  | 