CAST PRO Heat Detector
CAST PRO Heat Detector is backordered and will ship as soon as it is back in stock.
Couldn't load pickup availability
                    
                      Description
                      
                      
    
                    
                  
                  Description
- A programmable CAST-PRO heat detector.
 - Certified to EN54-5, 13 & 17 by Kiwa Telefication.
 - Compatible with C-TEC’s ZFP and XFP CAST protocol addressable fire panels.
 - Onboard short circuit loop isolator.
 - Includes two 8mm x 2mm ultra-bright red LED indicating strips.
 - Three operation modes – can be programmed to operate as an A1R, A2 or B heat detector.
 - <1mA alarm current.
 - 570A typical quiescent current @ 40V DC.
 - Compatible with C-TEC’s CA408 CAST base c/w integrated locking mechanism & ID tag.
 
Technical specifications
| Approvals/certifications | 
 Certified to EN54-13 by Kiwa Telefication., CPR number 0063-CPR-242190023, Kiwa Telefication certified to EN54-5 & 17  | 
|---|---|
| Compatibility | 
 Compatible with C-TEC's XFP/ZFP CAST Protocol Addressable Fire Panels.  | 
| Type | 
 Class A1R, Class A2 or Class B Heat (Programmable).  | 
| Sensitivity | 
 3 Detection Modes (class A1R, A2 or B heat, default is Class A2).  | 
| Supply wiring | 
 2-wire, polarity sensitive.  | 
| Supply/operating voltage | 
 22 to 40V DC.  | 
| Quiescent current | 
 570uA @ 40V.  | 
| Alarm current (Imax at Vmin) | 
 <1mA.  | 
| Alarm current (Iavg at Vmin) | 
 <1mA.  | 
| Sound pressure level (LAFmax) at Vmax at 1m | 
 N/A.  | 
| VAD category & coverage | 
 N/A.  | 
| Indicators | 
 2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.  | 
| Connections | 
 Via CA408 base: 1 +Ve IN (analogue switch); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.  | 
| Product dimensions (mm) | 
 105mm diameter x 48mm deep (detector only); 105mm diameter x 65mm deep (detector in base).  | 
| IP Rating | 
 IP21C  | 
| Weight | 
 118g (not in base); 172g (in base).  | 
| Operating conditions/temperature | 
 -10ºC to +50ºC. Max relative humidity: 95% (non-condensing)  | 
| Notes | 
 Requires a CA408 CAST base. CA408R relay base also available.  | 
Download Data Sheets
Click the PDF to download each individual data sheet.
            