ActiV C Class Base sounder VAD WHITE
ActiV C Class Base sounder VAD WHITE is backordered and will ship as soon as it is back in stock.
Couldn't load pickup availability
                    
                      Description
                      
                      
    
                    
                  
                  Description
- Third-party certified to EN54-3 (Sounders) and EN54-23 (VADs).
 - Provides ‘C-3-8.5’ light distribution (min 0.4 lux over a 3 x 8.5m cylindrical area).
 - Impressive 96dB(A) sound output @ 1m.
 - Includes 31 selectable primary tones and an optional secondary tone.
 - Two volume levels (high and low)
 - Three selectable VAD flash rates (0.5Hz, 1Hz, OFF)
 - Alarm Current at 30Vdc = 12.2mA (0.5Hz) or 19.5mA (1Hz)
 - Alarm Current at 18Vdc = 14.5mA (0.5Hz) or 25mA (1Hz)
 - Optional BF330CTLIDW white or BF330CTLIDR red cap available for stand-alone use.
 - Supplied with a BF431QCP quick connect plate and detector spur wires.
 - IP21C rated.
 
Technical Specifications
| Approvals/certifications | 
 Certified to EN54-3 & 23 by the LPCB  | 
|---|---|
| Protocol/compatibility | 
 Compatible with C-TEC's CFP, FP, MFP and EP203 conventional fire alarm panels and virtually all other makes (testing on third-party panels is recommended before use)  | 
| Application/operation | 
 Designed to be ceiling mounted – either stand-alone with a red or white cap or as part of a stacked Sounder/VAD/Detector Base combination.  | 
| VAD category & coverage | 
 C-3-8.5 (151m3 cylindrical coverage).  | 
| Flash rate & colour | 
 0.5Hz; 1Hz or OFF / White.  | 
| Supply/operating voltage | 
 18 to 30V DC.  | 
| Nominal SPL (Sound Pressure Level) | 
 96dB(A).  | 
| Alarm current | 
 At 30Vdc: 12.2mA (0.5Hz) or 19.5mA (1Hz); At 18Vdc: 14.5mA (0.5Hz) or 25mA (1Hz)  | 
| Product dimensions (mm) | 
 122mm diameter x 46mm deep (not including optional detector and base).  | 
| IP Rating | 
 IP21C (Type A).  | 
| Weight | 
 170g.  | 
| Operating conditions/temperature | 
 -10ºC to +55ºC. Max. 95% RH (Non-condensing).  | 
| Notes | 
 For compliance to EN54-3 & EN54-23, the BF431QCP Quick Connect Plate must be used with the base device.  | 
Download Data Sheets
Click the PDF to download each individual data sheet.
            
      
      